top of page

JFI Fire System Upgrade

SECTORS:

GAS & FUEL, AIRPORTS

CLIENT:

Sydney Airport

REGION:

NSW

STATUS

In Progress

COMPLETION DATE:

The project involves a comprehensive fire safety upgrade at JFI Sydney Airport fuel tanks to deliver enhanced cooling, foam and fire water infrastructure.


Scope of Works


  • Scope 1 Cooling Water Upgrades - Upgrades to cooling water systems for Tanks 4, 5, 6 & 7 to support neighbouring-tank   fire scenarios. Works include fabrication and installation of cooling water   rings and associated supply pipework. All mechanical works are above ground   at roof/perimeter level and are designed to avoid hot works on tank   roofs/shells.

  • Scope 2 New   Foam Water System - Design   and construct a new F3 environmentally friendly foam water system. This will   be commissioned before decommissioning the existing C6 system to ensure   continuous firefighting capability throughout the works.

  • Scope 3 Fire Water Storage & Pumps - Construct a new 675 kL fire water storage tank as backup during maintenance or main tank failure. Includes installation of redundant fire water pumps (one diesel and one electric) in accordance with AS1940-2017, delivering the final compliant upgrade solution.